4 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Publication 2711P-IN001I-EN-P - November 2009
Hazardous Locations
This equipment is suitable for these locations:
Class I, Division 2 Groups A, B, C, D
Class II, Division 2 Groups F, G
Class III
Ordinary, nonhazardous locations only
The following statement applies to use in hazardous locations.
The terminals have a temperature code of T4 when operating in a 55 °C (131 °F) maximum
ambient temperature. Do not install the terminals in environments where atmospheric gases
have ignition temperatures less than 135 °C (275 °F).
WARNING
Explosion Hazard
Substitution of components may impair suitability for hazardous locations.
Do not disconnect equipment unless power has been switched off and area is
known to be nonhazardous.
Do not connect or disconnect components unless power has been switched off.
All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. section
18-1J2 as appropriate.
Peripheral equipment must be suitable for the location in which it is used.

Other manuals for Rockwell Automation PanelView Plus 700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PanelView Plus 700 and is the answer not in the manual?

Rockwell Automation PanelView Plus 700 Specifications

General IconGeneral
BrandRockwell Automation
ModelPanelView Plus 700
CategoryTouch terminals
LanguageEnglish

Related product manuals