The graph shows the response of a single Power Module to severe overloads. As the load is
increased the power supply protection mechanism operates and shuts down the output. It
can be seen that for a period of just in excess of 200 ms the Power Module can provide
currents up to 115 A or 380 % of its stated maximum(115/31 = 3.8). This 200 ms/380 % can
be extrapolated for additional power supplies in order to perform MCB discrimination
studies.
4.2. Input Specification
Parameter Min Type Max Unit Condition
Input Voltage 90 264 Vac
Input Frequency 47 63 Hz
Inrush Current (peak) per Pack 50
<25
A
A
Full load
No load
Input current 0.2 A No load
Power Factor 0.95 0.99 > 50 % of full load
Input Leakage Current 1.7 mA 264 Vac, 50Hz
Lighting Surge and Transients
(damage free operation)
IEC 61000-4-5 Level 3
IEC 61000-4-4 Level 3
Hold Up Time 20 ms At 600 W
EMC (conducted) CISPR22 Class B,
EN 55022 Class B, with 3dB
margin
Table 3 Input Specification
4.3. Line Harmonics
Active power factor correction circuitry ensures that this Power Pack meets the
requirements of IEC 61000-3-2.