Check measurement
The GasSolarUnit/GasCompactUnit is
equipped with a simply selected automatic
function for check measurements (e.g.
emissions test).
These are described in the abridged operating
instructions and in detail in the separate
“Operating instructions for heating contractors
“ROTEX control unit” (see also the schematic
diagram in Fig. 9.2).
Pressing the Manual key (pos. 13 in Fig.
4.1.1) ramps up the boiler to its maximum
boiler water temperature for 20 min. Pressing
the key a second time during that runtime
switches the burner back to minimum load.
The runtime for this setting will start again at
20 minutes. Pressing the key again during the
20 min. period terminates the emission test.
008.1507644 · Subject to technical modifications· 06/2006 · In case of discrepancies, the original manual shall apply · 008.1507649 · 12/2005
Chapter 9:For the flue gas inspector
Burner load Rated output Flue gas mass flow rate Flue gas temperature Available draught
in kW in kW in g/s in °C in Pa
40/30 °C 80/60 °CNatural gas E,HNatural gas LL,LLPG 40/30 °C 80/60 °C
5.5 5.9 5.5 2.31 2.31 2.09 35 65 30
10.0 10.7 10.0 4.20 4.43 3.80 37 68 110
15.0 16.0 14.9 6.30 6.31 5.71 40 72 170
20.0 21.1 19.8 8.40 8.41 7.61 43 74 200
25.5 26.8 25.0 10.71 10.73 9.70 46 78 200
8.5 9.0 8.0 3.57 3.58 3.23 41 71 40
15.0 15.9 14.8 6.30 6.31 5.71 43 74 120
20.0 21.1 19.6 8.40 8.42 7.61 46 78 180
25.0 26.2 24.4 10.50 10.52 9.51 49 80 200
30.0 31.2 29.2 12.60 12.62 11.41 51 82 200
36.1 37.2 35.0 15.16 15.19 13.73 52 84 200
Table 9.1: Triple value for sizing the chimney (CO
2
adjustment in accordance with Table 5.1.2 or Fig. 5.1.7 and Fig. 5.1.8)
Fig. 9.1: Flue gas mass flow/burner output ROTEX GasSolarUnit/GasCompactUnit
Flue sizing details
ROTEX Heating Systems GmbH
Langwiesenstraße 10 · D-74363 Güglingen
Tel +49(7135)103-0 · Fax +49(7135)103-200
e-mail info@rotex.de · www.rotex.de
Fig. 9.2: Abridged manual using symbols
Emissions test mode
Current heat source
temperature
Remaining time
from activation
Cancel emissions test prematurely
Current heat source
temperature
Remaining time
from activation
GSU 25/
GCU 25
GSU 35/
GCU 35