R6 Series Solar Inverter
24
Figure 5.2
Electrical terminals of R6-5~10K-S3
Item
Name
A
DC Switch
B
DC Input
C
Relief Valve
D
RS232 Communication (Wi-Fi /4G)
E
RS485 Communication + DRM
F
AC Output
G
Ground Connection
Specifications for interface
5.3 Connection of Additional Grounding
WARNING
· The ground connection of this additional grounding connection cannot replace the AC cable PE terminal connection.
· Connect this additional grounding cable before AC cable connection, DC cable connection and communication cable
connection.
Note: The additional cable and OT/DT terminal should be prepared by user themselves.
Figure 5.3
Preparing additional grounding cable
1. Heat shrink tubing 2. OT/DT terminal
Note: Recommended conductor
cross-sectional area of additional
grounding cable is 6-16mm².
Remove the screw of grounding terminal
and secure the additional grounding cable
by insert a screw into the screw hole in the
OT/DT terminal.
Figure 5.3
Preparing additional grounding cable
1
2