Differential Pressure Monitor Owner’s Manual
Procedure if DOOR SW MODE is set to NOPEN.
1. Verify that DOOR SWITCH = YES.
2. Verify that DOOR SW MODE = NOPEN.
3. Connect the jumper wire between monitor screw terminals 3 and 4 for the
DOOR POSN (Point 32). See
Figure 4-1 for location of the screw terminals.
•
•
•
•
Verify that DOOR POSN is OPEN, indicating a contact closure.
4. Remove the jumper wire from one of the terminals.
Verify that DOOR POSN is CLOSED.
5. If DOOR POSN does not toggle OPEN and CLOSED, contact your local Siemens
Building Technologies representative.
Procedure if DOOR SW MODE is set to NCLOSE.
1. Verify that DOOR SWITCH = YES.
2. Verify that DOOR SW MODE = NCLOSE.
3. Connect the jumper wire between monitor screw terminals 3 and 4 for the
DOOR POSN point. See
Figure 4-1 for location of the screw terminals.
Verify that DOOR POSN is CLOSED, indicating a contact closure.
4. Remove the jumper wire from one of the terminals.
Verify that DOOR POSN is OPEN.
5. If DOOR POSN does not toggle OPEN and CLOSED, contact your local Siemens
Building Technologies representative.
24 Siemens Building Technologies, Inc.