Configuration instructions
3.2 Startup class
3RW44 soft starters
24 Manual, 03/2017, NEB535219502000/RS-AB/008
Application examples for very heavy starting (CLASS 30)
Heavy starting CLASS 30 (up to 60 s with 350 % I
n
motor
)
The soft starter has to be selected two power classes higher than that of the implemented
motor.
Voltage ramp and
current limiting
• Starting voltage %
30 50 50 30
• Starting time s
60 60 60 60
• Current limiting
value
4 x I
M
4 x I
M
4 x I
M
4 x I
M
Torque ramp
• Starting torque
20 50 50 20
• End torque
150 150 150 150
• Starting time
60 60 60 60
Note
The settings and device dimensions indicated in these tables are examples only; they are
merely provided for information purposes and are not binding.
Set values depend on the
application in question and must be optimized during commissioning.