Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Smart Infrastructure Engineering 2019-04-09
2.5 Equipment combinations
2.5.1 2-port / 3-port threaded valves with stroke actuator SAS..
Typical applications:
· Heating plants
· District heating plants
· Ventilation and air conditioning plants
Actuators
Stroke
Positioning force
Data sheet
SAS..
5.5 mm
400 N
N4581
PN 16 VVG44..
PN 16
VXG44.. SAS..
Medium 1…120 °C Medium 1…120 °C DN G k
vs
p
max
p
Data sheet N4364 Data sheet N4464 [Inch] [m
3
/h] [kPa] [kPa]
VVG44.15-..
1)
VXG44.15-..
1)
15 G 1 B 0.25 / 0.4 / 0.63 400 1600
VVG44.15-..
1)
VXG44.15-..
1)
15 G 1 B 1 / 1.6 400 725
VVG44.15-..
1)
VXG44.15-..
1)
15 G 1 B 2.5 / 4 400 400
VVG44.20-6.3 VXG44.20-6.3 20 G 1 1/4 B 6.3 400 750
VVG44.25-10 VXG44.25-10 25 G 1 1/2 B 10 400 400
VVG44.32-16 VXG44.32-16 32 G 2 B 16 250 250
VVG44.40-25 VXG44.40-25 40 G 2 1/4 B 25 125 125
PN 25 VVG55..
2)
SAS..
Medium 1…130 °C DN G k
v
s
p
max
p
Data sheet N4379 [Inch] [m
3
/h] [kPa] [kPa]
VVG55.15-..
1)
15 G 3/4 B 0.25 / 0.4 / 0.63 1200 2500
VVG55.15-..
1)
15 G 3/4 B 1 / 1.6 / 2.5 1200 2000
VVG55.20-4 20 G 1 B 4 1000 1000
VVG55.25-6.3 25 G 1 1/4 B 6.3 800 800
1)
.. = insert k
vs
value
2)
.. = VVG55 to be replaced by VVG549 as of January 1, 2017
2.5.2 2-port / 3-port threaded valves with stroke actuator SAS..
and SAT..
Typical applications:
· District heating plants
Actuators
Stroke
Positioning force
Data sheet
SAS..
5.5 mm
400 N
N4581
SAT..
5.5 mm
300 N
N4584
PN 25 VVG549..
SAS..
1), 2)
SAT..
1)
Medium 2...130 °C DN G k
vs
p
max
p
p
max
p
Data sheet Q4380 [Zoll] [m
3
/h] [kPa] [kPa] [kPa] [kPa]
VVG549.15-0.25
15 G 3/4 B
0,25
1200
2500
1200
2500VVG549.15-0.4 0,4
VVG549.15-0.63 0,63
VVG549.15-1 1
1500
1500VVG549.15-1.6 1,6
VVG549.15-2.5 2,5
VVG549.20-4K
3)
20 G 1 B 4
1600
1600
VVG549.25-6.3K
3)
25 G 1 1/4 B 6,3
1)
Briefly 150 °C (up to 150 °C max. 6 of 24 hours), with ALG..B fittings up to 100 °C
2)
SAS.. combined with VVG549: Change setting on the DIL switch to linear (factory setting = log).
SAS../MO: Change Modbus register 263 to 0 = linear ® only possible with Firmware release 2.0, not
with 0.27 and 1.0!
3)
Pressure compensated

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Acvatix SAS Series and is the answer not in the manual?

Siemens Acvatix SAS Series Specifications

General IconGeneral
BrandSiemens
ModelAcvatix SAS Series
CategoryController
LanguageEnglish

Related product manuals