3.13 Control parameters
A number of control parameters can be readjusted to optimize control performance.
This can be done on the thermostat via HMI or via commissioning / operating tool.
These parameters can also be set during operation without opening the unit.
In the event of a power failure, all control parameter settings are retained.
The control parameters are assigned to 2 levels:
“Service level”, and
“Expert level” including communications, diagnostics and test
The Service level” contains a small set of parameters to set up the thermostat for
the HVAC system and to adjust the user interface. These parameters can be
adjusted any time.
Change parameters at the “Expert level” carefully, as they impact the thermostat’s
control performance and functionality.
3.13.1 Parameter setting via local HMI
1. Press buttons + and simultaneously for 3 seconds. Release and press
button + again for 3 seconds within 2 seconds. The display shows
“P01”. Continue with step 2.
1. Press buttons + and simultaneously for 3 seconds. Release and press button
again for 3 seconds within 2 seconds. The display shows “P01” and service.
2. Repeatedly press the + or button to select the required parameter.
P01 P02 P08 P14
+- +
- -
+
3171z99
End
-
+
-
P13
+-
3. Press + and simultaneously. The current value of the selected parameter
begins to flash, allowing you to change the value by repeatedly pressing + or .
4. The next parameter is displayed when you press + and again simultaneously.
5. Repeat steps 2 to 4 to display and change additional parameters.
6. Press + or until “End” is displayed, and then press + and simultaneously to
save the change and exit parameter entry mode.
The factory setting for the control parameters can be reloaded via parameter P71,
by changing the value to “ON”, and confirming by pressing buttons + and
simultaneously. The display shows “8888” during reload.
3.13.2 Parameter setting / download via Modbus
communication tool
Control parameters can be adjusted via Modbus either by local HMI or Modbus
commissioning tools.
Please refer to section 4.2 for commissioning.
Enter only “Service”
level
Enter “Service” and
“Expert” level.
Adjust parameters
Reset parameters