Technical Specifications
5
This section provides important technical specifications related to the device.
5.1 Power Supply Specifications
Note
When determining cable lengths, make sure the minimum input voltage for the pow-
er supply is provided at the power source.
Input Range
Power Sup-
ply Type
Min Max
Internal
Fuse Rating
Maximum
Power Con-
sumption
a
Insulation
88 VDC 300 VDC
HI
85 VAC 264 VAC
3.15 A(T)
b
65 W
88 VDC 300 VDC
HIP
85 VAC 264 VAC
3.15 A(T)
b
65 W
2800 VDC
for 1 minute
24
24P
13 VDC 36 VDC 10 A(T)
b
63.5 W
48
48P
36 VDC 72 VDC 3.15 A(T)
b
60 W
1500 VDC
for 1 minute
12
12P
9 VDC 15 VDC 12 A 67 W
1500 VAC or
2121 VDC
for 1 minute
a
Power consumption varies based on the device configuration.
b
(T) denotes time-delay fuse.
5.2 Failsafe Relay Specifications
Maximum Switching Voltage Rated Switching Current Isolation
30 VDC 5 A
125 VDC 0.1 A
a
, 0.15 A
b
250 VAC 6.25 A
2800 VDC for 1 minute be-
tween coil and contacts
a
Inductive load R/L = 7 ms
b
Resistive load
RUGGEDCOM RX1510
Installation Manual, 12/2019, C79000-G8976-1055-16
43