Technical Specifications
5
This section provides important technical specifications related to the device.
5.1 Power Supply Specifications
Note
When determining cable lengths, make sure the minimum input voltage for the
power supply is provided at the power source.
Input Range
Power
Supply Type
Min Max
Internal
Fuse Rating
Maximum
Power
Consumption
a
Insulation
88 VDC 300 VDC
HI
85 VAC 264 VAC
3.15 A(T)
b
65 W
88 VDC 300 VDC
HIP
85 VAC 264 VAC
3.15 A(T)
b
65 W
2800 VDC
for 1 minute
24
24P
13 VDC 36 VDC 10 A(T)
b
63.5 W
48
48P
36 VDC 72 VDC 3.15 A(T)
b
60 W
1500 VDC
for 1 minute
12
12P
9 VDC 15 VDC 12 A 67 W
1500 VAC or
2121 VDC
for 1 minute
a
Power consumption varies based on the device configuration.
b
(T) denotes time-delay fuse.
5.2 Failsafe Relay Specifications
Maximum Switching Voltage Rated Switching Current Isolation
30 VDC 5 A
125 VDC 0.1 A
a
, 0.15 A
b
250 VAC 6.25 A
2800 VDC for 1 minute
between coil and contacts
a
Inductive load R/L = 7 ms
b
Resistive load
RUGGEDCOM RX1524
Installation Manual, 04/2021, C79000-G8976-1487-02