Certification
6.1.8Other Approvals
• China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic
Information Products
A copy of the Material Declaration is available online at https://
support.industry.siemens.com/cs/ww/en/view/109738831.
6.1.8 Other Approvals
This device meets the requirements of the following additional standards:
• IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
• IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
• IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General
Requirements
• NEMA TS-2
Traffic Controller Assemblies with NTCIP Requirements
6.2 EMC and Environmental Type Tests
The RUGGEDCOM RX1524 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Test for IEC 61850-3
Test Description Test Levels Severity
Levels
Enclosure Contact ± 8 kVIEC 61000-4-2 ESD
Enclosure Air ± 15 kV
4
IEC 61000-4-3 Radiated RFI Enclosure Ports 20 V/m
Signal ports ± 4 kV @ 2.5 kHz
Note
a
DC Power Ports
AC Power Ports
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports
± 4 kV 4
Signal ports ± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4IEC 61000-4-5 Surge
DC Power Ports ± 2 kV Line-to-Ground 3
52
RUGGEDCOM RX1524
Installation Manual, 04/2021, C79000-G8976-1487-02