EasyManuals Logo
Home>Siemens>Computer Hardware>SIMATIC 314C-2 DP

Siemens SIMATIC 314C-2 DP User Manual

Siemens SIMATIC 314C-2 DP
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #120 background imageLoading...
Page #120 background image
Technical data of CPU 31xC
6.3 CPU 313C
CPU 31xC and CPU 31x, Technical Data
6-8 Manual, 01/2006 Edition, A5E00105475-06
Reference
In Chapter
Specifications of the integrated I/O
you can find
the specifications of integrated I/Os under
Digital inputs of CPUs 31xC
and
Digital outputs
of CPUs 31xC
.
the block diagrams of the integrated I/Os under
Arrangement and usage of integrated
I/Os
.
6.3 6.3 CPU 313C
Technical data
Table 6-4 Technical data of CPU 313C
Technical data
CPU and version
Order no. [MLFB] 6ES7 313-5BE01-0AB0
Hardware version
01
Firmware version
V2.0.0
Associated programming package
STEP 7 as of V 5.2 + SP 1
(please use previous CPU for STEP 7 V 5.1 + SP
3 or later)
Memory
Work memory
Integrated
32KB
Expandable
No
Load memory Plugged in with MMC (Max. 8 MB)
Data storage life on the MMC
(following final programming)
At least 10 years
Buffering Guaranteed by MMC (maintenance-free)
Execution times
Processing times of
Bit operations
Min. 0.1 μs
Word instructions
Min. 0.2 μs
Fixed-point arithmatic
Min. 2 μs
Floating-point arithmatic
Min. 3 μs
Timers/counters and their retentive address areas
S7 counters 256
Retentive address areas
Configurable
Default
From C 0 to C 7
Counting range
0 to 999

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC 314C-2 DP and is the answer not in the manual?

Siemens SIMATIC 314C-2 DP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC 314C-2 DP
CategoryComputer Hardware
LanguageEnglish

Related product manuals