Hardware installation
3.4 Installing on a DIN rail
CP 5711
24 Operating Instructions, 12/2021, C79000-G8976-C283-08
3.4 Installing on a DIN rail
Condition
To mount the communications processor on a 35 mm DIN rail, you require an additional DIN
rail holder. You can obtain this holder under the article number 6GK1 571-1AA00-0AH0.
Safety notice
NOTICE
Improper mounting
Improper mounting may damage the device or impair its operation:
Before mounting the device, always ensure that there is no visible damage to the device.
Mount the device using suitable tools. Refer to the information in section "Technical
specifications (Page 29)".
WARNING
EXPLOSION HAZARD
When used in hazardous environments corresponding to Class I, Division 2 or Class I, Zone
2, the device must be installed in a cabinet or a suitable enclosure.
To comply with EU Directive 2014/34 EU (ATEX 114), UK-Regulation SI 2016/1107 or the
conditions of IECEx or CCC-Ex, the housing or cabinet must meet the requirements of at
least IP54 (according to EN/IEC 60529, GB/T 4208) in compliance with EN IEC/IEC 60079-7,
GB 3836.8.