Page #67 background imageLoading...
Page #67 background image
Technical specifications
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 120 x 145 x 125 mm
Weight 880 g
Installation options
Wall mounting
Installation on a DIN rail
Mounting on an S7-300 standard rail
Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 41 years
1)
Note the wiring rules (Page 51).
7.7 Mechanical stability (in operation)
Mechanical stability (in operation)
Device IEC 60068-2-27 shock IEC 60068-2-6 vibration
15 g, 11 ms duration
6 shocks per axis
10 - 58 Hz: 0.075 mm
85 - 150 Hz: 1 g
1 octave/min, 20 sweeps
SCALANCE XC206-2 (ST/BFOC)
SCALANCE XC206-2 (SC)
SCALANCE XC206-2SFP
SCALANCE XC208
SCALANCE XC216
SCALANCE XC224
7.8 Cable lengths
The cable lengths listed below apply to the SCALANCE XC-200.
Cable Permitted cable length
IE TP torsion cable
with IE FC Outlet RJ-45 + 10 m TP cord
0 to 45 m
+ 10 m TP cord
IE TP torsion cable
with IE FC RJ-45 Plug 180
0 to 55 m
Technical specifications
7.8 Cable lengths
SCALANCE XC-200
Operating Instructions, 12/2017, C79000-G8976-C442-03 67

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET SCALANCE XC208 and is the answer not in the manual?

Siemens SIMATIC NET SCALANCE XC208 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET SCALANCE XC208
CategorySwitch
LanguageEnglish

Related product manuals