5.2 OpenPCS 7 without OS
OpenPCS 7 station without installed OS client
In this configuration, the OpenPCS 7 station is installed without an OS client. The OPC clients
run on a separate PC. All OPC clients access the OpenPCS 7 station. The OpenPCS 7 station
contains the OPC DA, OPC HDA and OPC A&E servers.
This configuration is intended for large plants.
Plant bus
Terminal bus
Fieldbus
PCS 7 OS clients
OPC clients
PCS 7 OS server BATCH serverRoute Control server
Archive server
S7-400S7-400S7-400
ET 200ET 200ET 200
OpenPCS 7 Station
Construct redundant connections for OpenPCS 7 stations in PCS 7
No redundant OpenPCS 7 station is implemented in PCS 7.
You can create redundancy of sorts by running several identical OpenPCS 7 stations. This
requires that your OPC client has the following functionality:
Determination of the OpenPCS 7 station through which the necessary information is
available.
Detection of failure of an OpenPCS 7 station and failover to an available OpenPCS 7
station
System configurations
5.2 OpenPCS 7 without OS
OpenPCS 7
Function Manual, 05/2012, A5E02780178-02 33

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC OpenPCS 7 and is the answer not in the manual?

Siemens SIMATIC OpenPCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC OpenPCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals