severity "1" and priority "16" to OPC severity "1000". All other priority values are obtained by
linear interpolation between "0" and "1000".
6.5.6 Attributes of the PCS 7 OS message system
Attributes of the PCS 7 OS message system
The following table lists the OPC attributes and their meaning in the PCS 7 OS message
system. A PCS 7 OS message belongs to a message class and has system attributes, user
texts and process values. Some of the attributes of a PCS 7 OS message are only for internal
use in the PCS 7 OS and are therefore not relevant for an OPC A&E client. These attributes
are not listed in the table.
OPC attribute Meaning in the PCS 7 OS message system
ClassName Displays the message class name.
Type name Displays the message type name.
ForeColor Displays the text color for the display of received, sent and acknowledged
messages.
BackColor Displays the background color for the display of received, sent and acknowledged
messages.
FlashColor Displays the flashing color.
Flags Indicates whether the message requires acknowledgment.
Text01 Displays the content in the source.
Text02 Displays the content of the area.
Text03 Displays the content in the event.
Text04 Displays the batch name.
Text05 Displays the content of the operation message.
Text06 Displays the content of the text block "free 1".
Text07 Displays the content of the text block "free 2".
Text08 Displays the content of the text block "free 3".
Text09 Displays the content of the text block "free 4".
Text10 Displays the content of the text block "free 5".
ProcessValue01 Displays the content of ProcessValueBlock01.
ProcessValue02 Displays the content of ProcessValueBlock02.
ProcessValue03 Displays the content of ProcessValueBlock03.
ProcessValue04 Displays the content of ProcessValueBlock04.
ProcessValue05 Displays the content of ProcessValueBlock05.
ProcessValue06 Displays the content of ProcessValueBlock06.
ProcessValue07 Displays the content of ProcessValueBlock07.
ProcessValue08 Displays the content of ProcessValueBlock08.
ProcessValue09 Displays the content of ProcessValueBlock09.
ProcessValue10 Displays the content of ProcessValueBlock10.
StateText Displays the status message.
OpenPCS 7 interface
6.5 OPC Alarms and Events (OPC A&E)
OpenPCS 7
60 Function Manual, 05/2012, A5E02780178-02

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC OpenPCS 7 and is the answer not in the manual?

Siemens SIMATIC OpenPCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC OpenPCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals