Communication with the S7-300
5.3 Communication services on the MPI/DP interface (X1)
Reference
Further information
about setting the PG/PC interface for routing can be found in Getting Started
CPU 317T-2 DP: Controlling a SINAMICS S120
in chapter
Configuring the PG/PC
Interface
.
about routing can be found in the
Programming with STEP 7
manual, or directly to the
STEP 7
online help.
about configuring with
STEP 7
can be found in the
Configuring Hardware and
Connections in STEP 7
manual
fundamentals can be found in the
Communication with SIMATIC
Manual.
about TeleService adapters can be found at Internet website
http://www.ad.siemens.de/support with article ID 14053309 (documentation).
on SFCs can be found in the
Instruction list
, for more details refer to the
STEP 7 online
help
or to the
System and Standard Functions
reference manual.
on communication can be found in the
Communication with SIMATIC
manual.
5.3.8 Data consistency
Properties
A data area is consistent if it can be read or written to from the operating system as a
consistent block. Data exchanged collectively between the stations should belong together
and originate from a single processing cycle, that is, be consistent.
If the user program contains a programmed communication function, for example, access to
shared data with XSEND/ XRCV, access to that data area can be coordinated by means of
the "BUSY" parameter itself.
With PUT/GET functions
For S7 communication functions, such as PUT/GET or write / read via OP communication,
which do not require a block in the user program on the CPU (operating in server mode),
allowances must be made in the program for the extent of the data consistency.
The PUT/GET functions for S7 communication, or for reading/writing variables via OP
communication, are executed at the CPU's scan cycle checkpoint.
In order to ensure a defined process interrupt reaction time, communication variables are
copied consistently in blocks of maximum 160 bytes to/from the user memory at the scan
cycle check point of the operating system. Data consistency is not guaranteed for larger data
areas.
Note
Where defined data consistency is required, the length of communication variables in the
CPU's user program may not exceed 160 bytes.
S7-300 CPU Data: CPU 315T-2 DP
Manual, 12/2005, A5E00427933-02
5-13

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP and is the answer not in the manual?

Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-300 CPU Data: CPU 315-T-2 DP
CategoryControl Unit
LanguageEnglish

Related product manuals