2.2 Basic Start-up (Regenerative Rectifier without
Autotransformer)
P051 = 2
P053 = 6
P052 = 5
P071 = 460
P320 = 20
P773 = 1.00
P051=2
Select “Basic Mode Settings”
P053 =6 Access Parameter
P052 = 5
Drive Settings
P071 = Input Rectifier Voltage
Generally = 460 Volt
P320 = 20
Smooth Load Amps, to
prevent input line sags
from effecting the DC BUS
regulator
P773= 1.00
Deadband Converter, to
prevent “toggling” between
Regen and Rectifier
bridges.