2 Functions
286
7UT613/63x Manual
C53000-G1176-C160-2
spective measuring location or side (in case of earth faults, below the smallest fault
current). This parameter can only be altered in DIGSI at Additional Settings.
In address 8403 FUSE FAIL MON. the fuse-failure monitor, in case of asymmetrical
tests, for example can be switched off.
Three-phase Mea-
sured Voltage
Failure (Fuse-
failure Monitor)
At address 8426 FFM U<max (3ph) the minimum voltage is set. If the measured
voltage drops below this threshold and a simultaneous current jump is not detected
while all three-phase currents are greater than the minimum current required for the
impedance measurement by the distance protection according to (addresses 1111 to
1142) a three-phase measured voltage failure is recognised. This parameter can only
be set with DIGSI at Additional Settings.
2.19.1.5 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
8101 BALANCE I ON
OFF
OFF Current Balance Supervi-
sion
8102 BALANCE U ON
OFF
OFF Voltage Balance Supervi-
sion
8104 SUMMATION U ON
OFF
OFF Voltage Summation Su-
pervision
8105 PHASE ROTAT. I ON
OFF
OFF Current Phase Rotation
Supervision
8106 PHASE ROTAT. U ON
OFF
OFF Voltage Phase Rotation
Supervision
8111 BAL. I LIMIT M1 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 1
5A 0.50 .. 5.00 A 2.50 A
8112 BAL. FACT. I M1 0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.1
8113A T Sym. I th. M1 5 .. 100 sec 5 sec Symmetry Iph: Pick-up
delay
8121 BAL. I LIMIT M2 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 2
5A 0.50 .. 5.00 A 2.50 A
8122 BAL. FACT. I M2 0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.2
8123A T Sym. I th. M2 5 .. 100 sec 5 sec Symmetry Iph: Pick-up
delay
8131 BAL. I LIMIT M3 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 3
5A 0.50 .. 5.00 A 2.50 A
8132 BAL. FACT. I M3 0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT613 series and is the answer not in the manual?

Siemens SIPROTEC 7UT613 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT613 series
CategoryProtection Device
LanguageEnglish

Related product manuals