4 Technical Data
442
7UT613/63x Manual
C53000-G1176-C160-2
4.4 Time Overcurrent Protection for Phase and Residual Currents
Characteristics
Current Stages
Definite-time stages DT I
Ph
>>, 3I
0
>>, I
Ph
>, 3I
0
>
Inverse time stages
(acc. to IEC or ANSI)
IT I
P
, 3I
0P
one of the tripping curves depicted in figures
to 4-12 on the right-hand side may be select-
ed;
alternatively user specified trip and reset char-
acteristic
Reset characteristics
(with disk emulation)
IT For illustrations of possible reset time charac-
teristics see figures to 4-12 on the left-hand
side.
High current stages I
Ph
>> 0.10 A to 35.00 A
1)
or ∞ (ineffective)
Steps 0.01 A
T
IPh>>
0.00 s to 60.00 s
or ∞ (no trip)
Steps 0.01 s
3I
0
>> 0.10 A to 35.00 A
1)
or ∞ (ineffective)
Steps 0.01 A
T
3I0>>
0.00 s to 60.00 s
or ∞ (no trip)
Steps 0.01 s
Definite time current elements
(50Ns-2, 50Ns-1)
I
Ph
> 0.10 A to 35.00 A
1)
or ∞ (ineffective)
Steps 0.01 A
T
IPh>
0.00 s to 60.00 s
or ∞ (no trip)
Steps 0.01 s
3I
0
> 0.10 A to 35.00 A
1)
or ∞ (ineffective)
Steps 0.01 A
T
3I0>
0.00 s to 60.00 s
or ∞ (no trip)
Steps 0.01 s
Inverse current elements (51Ns-
IEC)
I
P
0.10 A to 4.00 A
1)
Steps 0.01 A
T
IP
0.05 s to 3.20 s
or ∞ (no trip)
Steps 0.01 s
3I
0P
0.05 A to 4.00 A
1)
Steps 0.01 A
T
3I0P
0.05 s to 3.20 s
or ∞ (no trip)
Steps 0.01 s
Inverse current elements (51Ns-
ANSI)
I
P
0.10 A to 4.00 A
1)
Steps 0.01 A
D
IP
0.50 s to 15.00 s
or ∞ (no trip)
Steps 0.01 s
3I
0P
0.05 A to 4.00 A
1)
Steps 0.01 A
D
3I0P
0.50 s to 15.00 s
or ∞ (no trip)
Steps 0.01 s
Tolerances with inverse time
2)
currents 3 % of set value or 1 % rated current
times 1 % of set value or 10 ms
Tolerances with definite time (IEC)
2)
currents Pickup at 1.05 ≤ I/I
P
≤ 1.15;
or 1.05 ≤ I/3I0P ≤ 1.15

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT613 series and is the answer not in the manual?

Siemens SIPROTEC 7UT613 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT613 series
CategoryProtection Device
LanguageEnglish

Related product manuals