3 SPECIFICATION
Table 2 Technical Parameters
Items
Contents
Working Voltage
DC8. 0V to 35. 0V, Continuous Power Supply.
Overall Consumption
<3W (Standby mode: ≤2W)
AC voltage Input:
3 Phase 4 Wire
3 Phase 3 Wire
Single Phase 2 Wire
2 Phase 3 Wire
AC15V - AC360V (ph-N)
AC30V - AC620V (ph-ph)
AC15V - AC360V (ph-N)
AC15V - AC360V (ph-N)
Alternator Frequency
50Hz/60Hz
Speed Sensor Voltage
1.0V to 24V (RMS)
Speed Sensor Frequency
10,000Hz (max)
Start Relay Output
5A DC28V power supply
Auxiliary Relay Output 1
5A DC28V power supply
Auxiliary Relay Output 2
5A DC28V power supply
Auxiliary Relay Output 3
5A DC28V power supply
Auxiliary Relay Output 4
5A DC28V voltage-free output
Auxiliary Relay Output 5
5A DC28V voltage-free output
Overall Dimensions
126mm x 109mm x 44mm
Panel Cutout
110mm x 90mm
CT Secondary Current
5A (rated)
Working Temperature
(-25~+70)°C
Working Humidity
(20~93)%RH
Storage Temperature
(-25~+70)°C
Protection Level
IP55 Gasket
Insulation Intensity
Apply AC2.2kV voltage between high voltage terminal and low
voltage terminal; The leakage current is not more than 3mA within
1min.
Weight
0.26kg