-50-
No.PS※※-OML0003-J
○ Faults and countermeasures
1
•Output remains
ON.
Indicator LED
remains ON.
•Output remains
OFF.
Indicator LED
remains OFF.
Incorrect pressure
setting
(1) Check the set pressure.
(2) Check the operation mode,
hysteresis and output type.
(hysteresis mode / window
comparator mode, normal /
reversed output)
(1) Reset the pressure
setting.
(2) Reset the function
settings.
2
Output remains
ON.
Indicator LED
works correctly.
Incorrect wiring
Check the wiring of the output.
Check if the load is connected
directly to DC(+) or DC(-).
Correct the wiring.
3
Output remains
OFF.
Indicator LED
works correctly.
Incorrect wiring
Check the wiring of the output.
Check if the load is connected
directly to DC(+) or DC(-).
Correct the wiring.
Unsuitable model
selection
Check if PNP is used when NPN
should have been selected, or the
other way around.
Review the selected model
(output type).
Broken lead wire
Check if there is bending stress
applied to any parts of the lead wire.
(bending radius and tensile force
applied).
Correct the wiring
conditions. (adjust the
tensile force and increase
the bending radius).
4
Switch output
generates
chattering.
Incorrect wiring
Check the wiring.
Check that the brown and blue wires
are connected to DC(+) and DC(-)
respectively, and if the output wiring
is loose (contact failure).
Correct the wiring.
Incorrect settings
(1) Check the set pressure.
(2) Check that the hysteresis range
is not too narrow.
(3) Check the response time set at
initial setting.
Check that the response time is
not too short.
(1) Reset the pressure
setting.
(2) Increase the hysteresis.
(3) Reset the function
settings.
5
Slow switch
output response
Incorrect pressure
setting
Check the pressure setting.
Check that the detected pressure
and the set pressure value are not
the same or not too close.
Reset the pressure setting.
Set the pressure setting
value so it is not too close
to the detected pressure.