-51-
No.PS※※-OML0003-J
Fault No.
Fault
Possible cause
Investigation method
Countermeasure
6
Analogue output
(OUT2) is not
provided.
(specified
accuracy is not
satisfied).
Incorrect wiring
Check that the analogue output
(OUT2) is connected to a load.
Correct the wiring.
Non-compliance
with the load
specification.
(1) Check that the correct load is
connected.
(2) Check that the impedance of the
input equipment (A/D
transformer) is suitable.
Connect a suitable load.
Insufficient
warm-up time
Check if the product satisfies the
specified accuracy after 10 minutes
warm up time.
After energizing, the display
and output can drift. For
detecting fine pressures,
warm up the product for 10 to
15 minutes.
Product failure
Replace the product.
7
An over current
error (Er1, Er2)
is displayed.
System error
(Er0, Er4, Er6,
Er7, Er8 or Er9)
is displayed.
The display
shows "HHH".
The display
shows "LLL".
Residual
pressure error
(Er3) is
displayed.
Over current to
the output
(Er1, Er2)
(1) Check that the switch output load
current is not more than 80 mA.
(2) Check that the connected load
satisfies the specifications, and
check the load for short circuits.
(3) Check that any relay is connected
with a surge voltage suppressor.
(4) Check if the wiring is not in the
same route as (or bundled
together with) a high voltage
cable or power cable.
(1)(2) Connect the load as
specified.
(3) Use a relay with a surge
voltage suppressor or
take measures to
prevent noise.
(4) Separate the wiring route
from any high voltage
cable or power cable.
Incorrect
operation of the
internal data of
the Pressure
switch
(Er0, Er4, Er6,
Er7, Er8, Er9)
(1) Check that there is no noise
interference such as static
electricity, and check for noise
sources.
(2) Check that the power supply
voltage is within the range 12 to
24 VDC ±10%.
(1) Remove the noise and the
noise source (or take
measures to prevent noise
interference), and reset
the product, or turn off the
power supply and turn it
on again.
(2) Supply a correct voltage
of 12 to 24 VDC ±10%.
Applied
pressure is
above the upper
limit (HHH).
(1) Check that the pressure is not
above the upper limit of the set
pressure range.
(2) Check that foreign matter has not
entered the piping.
(1) Adjust the pressure to
within the set pressure
range.
(2) Take measures to prevent
foreign matter from
entering the piping.
Applied
pressure is
below the lower
limit (LLL).
(1) Check that the pressure is not
below the lower limit of the set
pressure range.
(2) Check that foreign matter has not
entered the piping.
(1) Adjust the pressure to
within the set pressure
range.
(2) Take measures to prevent
foreign matter from
entering the piping.
Pressure is not
atmospheric
pressure at
zero-clear
operation (Er3)
Check that during the zero clear
operation, pressure above ±7%F.S.
(±3.5%F.S. for compound pressure)
was not applied.
Return the applied pressure
to atmospheric pressure,
and retry the zero clear
operation.
Product failure
Replace the product.

Other manuals for SMC Networks ZSE30A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks ZSE30A series and is the answer not in the manual?

SMC Networks ZSE30A series Specifications

General IconGeneral
BrandSMC Networks
ModelZSE30A series
CategorySwitch
LanguageEnglish

Related product manuals