Appendix A: Troubleshooting
SolarEdge Power Optimizers Installation Guide – MAN-01-00112-1.2
18
Appendix A: Troubleshooting
For Installations with SolarEdge Inverters
Problem
Possible Cause
Possible Solution
String voltage is 0V
Output of one or more power
optimizers is disconnected
Co
nnect all power optimizer outputs
String voltage not 0V but
lower than no. of
optimizers
One or more of the power
optimizers are not connected
in the string
Connect all power optimizers
One or more of the modules
are not connected properly to
their powe
r optimizer inputs
Connect the modules to the optimizer
inputs
Wrong polarity connection on
one of the strings
Check polarity of the string output using
a voltmeter and correct if needed.
String voltage higher than
the number of optimizers
WARNING!
If the measured
voltage is too high, the
installation may not have a
safe low voltage.
PROCEED WITH CARE!
A deviation of
±1% per
string is reasonable.
Si la tension mesuree est
trop haute, la tension basse
de securite pourrait
manquer dans l’installation.
REDOUBLEZ DE
PRECAUTION.
Une deviation de
±1%
par
string est raisonnable.
An extra power optimizer is
connected in the string
Check if an extra power optimizer is
connected in the string. If not
proceed
to next solution.
A module is connected directly
to the string, without a power
optimizer.
Verify that only power optimizers are
connected in the string and that no
module outputs are connected without
a power optimizer. If the problem
persists, proceed to the next step.
A malfunction of one of the
power optimizers
x
Disconnect the wires that connect
the power optimizers in the string.
x Measure the output voltage of
each power optimizer in order to
locate the power optimizer that
does not output the 1V safety
voltage.
x If a malfunctioning power
optimizer is located, check its
connections, polarity, module and
voltage.
x If a malfunction cannot be
bypassed or resolved, skip the
malfunctioning power optimizer,
thus connecting a shorter string.
x Do not continue before finding
the problem and replacing the
malfunctioning power optimizer.
SafeDC mode was disabled
using the SolarEdge Key
Enable the SafeDC.