Appendix A: Troubleshooting
SolarEdge Power Optimizers Installation Guide – MAN-01-00112-1.2
For Installations with Non-SolarEdge Inverters
Diagnostics/Possible Solution
Output of one or more power
optim
Check/connect all power optimizer
outputs
PV Modules are connected to
power optimizers with reversed
polarity
Check the PV module polarity using a
voltmeter, and correct if needed
Fuse is blown / DC circuit breaker
is disconnected
Replace the fuse, or connect DC
circuit breaker. The Fuse/Circuit
breaker should support current of
15A or higher
String voltage is lower
than minimum input
voltage of the inverter
Insufficient number of modules
in the string
Verify that the number of
connected in the string is according
to the inverter's design rules.
Refer to the Inverter Manual or PV
module datasheets to determine
minimum string length
One or more of the power
optimizers are not connected in
the string
Wait ~30sec until all optimizers
Measure the string output using
If the string output is less than
the number of optimizers, check
and/or connect all power
optimizers
For installations without safety &
monitoring interface
connect all power optimizers
Wrong polarity connection on
one of the strings
Check polarity of the string output
using a voltmeter and correct if
needed.