FPS-900-RS O&M Manual
Version: 3; 3/2020
Page 8 of 28
4. Site and Utility Requirements
4.1. Air Supply
The N
2
-BLAST
®
FPS-900-RS includes a built-in air compressor to supply gas to the nitrogen generator.
It is not for performing quick fills. Please install a separate suitable air compressor for other needs.
4.2. Additional Piping and Hosing
Sourcing and installing additional plumbing, supplied by other manufacturers, must meet all of the unit’s
flow, pressure, and temperature requirements. If piping length between any equipment is greater than
50 feet, consult with a piping contractor for proper line size.
4.3. Electrical Requirements
The N
2
-BLAST
®
FPS-900-RS requires 120VAC / 50-60hz / Single Phase (1Ф). A 240VAC option is also
available. It has a built-in 10Amp fuse and comes with hard wire to terminal blocks for customer
connection. It comes with UL 508A ICP certification and the electrical schematics are available upon
request.
4.4. Site Specifications
Unless designed otherwise, install in a nonhazardous indoor location with temperatures between 40-
100°F (4°- 38°C).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the South-Tek Systems N2 Blast FPS-900-RS and is the answer not in the manual?

South-Tek Systems N2 Blast FPS-900-RS Specifications

General IconGeneral
BrandSouth-Tek Systems
ModelN2 Blast FPS-900-RS
CategorySafety Equipment
LanguageEnglish

Related product manuals