5.5Electricalconnections
5.5.1TA450-1400EL
TerminalblockDescriptionRemark
1PE
Ground
2N
Earthedneutral(supplyvoltage)
Notusedwhen230V3~
3L1
Phase(supplyvoltage)
230V1~
4L2
Phase(supplyvoltage)
-
5
L3
Phase(supplyvoltage)
-
400V3~/
230V3~
6-8Internalconnecting
*9
DI1
ThermalContactfan
Normallyclosed
10
TC(seriesconnect.withext.Fan)
*11DIrefThermalContactfan
12L1
Externalfan
13N
ExternalfanSeechapter6.2
14230VFanspeed
15180VFanspeed
16160VFanspeed
17130VFanspeed
18AI1
Sensorsupplyairtemp
PT1000
19
AIrefSensorsupplyairtempreference
*20DIrefExtended/Forcedrunning
*21
DI3
Extended/Forcedrunning
Normallyopen
22
DOrefOutdoorairdamper
23
DO3Outdoorairdamper24VAC,0,5A
24
GSupplyvoltagevalveactuator,Cooling24VAC
25
G0Supplyvoltagevalveactuator,Cooling
Neutral
*26DIrefFirealarm(digitalinput)
*27
DI4
Firealarm(digitalinput)
Normallyclosed
28
DOrefAlarmOutput
29
DO4AlarmOutput24VAC,0,5A
30
AO2Cooling0-10VDC
31AI4
Sensoroutdoorairtemp
PT1000
32
AIrefSensoroutdoor/extractairtempreference
33AI2
Sensorextractair
PT1000
*Theseinputsmayonlybewiredtopotentialfreeconnectors.
TA450-4500Installationinstructions
132615
14
SystemairSverigeAB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir TA 2000 HW and is the answer not in the manual?

SystemAir TA 2000 HW Specifications

General IconGeneral
BrandSystemAir
ModelTA 2000 HW
CategoryFan
LanguageEnglish

Related product manuals