Installation |
25
9.3 Connect the condensation drain
Connect the drainage pipe and drain trap on the exhaust air side at the bottom of the unit, figure 8. Cut the drainage
pipe to required height, see table 3.
Note:
When installed in a non heated place the drain pipe and trap needs to be insulated well to prevent the water
from freezing.
Fig. 8
H
32
60
(mm)
Table 3
H (mm) Max. Negative pressure (Pa)
100 300
135
1
600
180 1000
1
Normal conditions