Page #16 background imageLoading...
Page #16 background image
15
8. CONTROL OPERATION
Based on different purposes for setting the switch cords on the PC
panel of the indoor electrical control box. Once you complete the
settings, please restart the main power supply for the settings to
become active.
8.1 Horsepower settings
Horsepower code
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
ENC1
PO WER_S
8.2 Network address settings
1) The network address is set based on communication
between the indoor and outdoor units. The address is the same
as the indoor address, and there is no need to set them
separately.
2) The central control of indoor units can be done on an
outdoor unit. There is no need to control indoor unit separately.
3) For previous control of the indoor units, the network can be
set by connecting (X, Y, E) terminals. There is no need to set
the network address. The network can also be set by outer
network module and main board (CN20).
The system has a total of 64 units (0-63). Each has only one
system address code. If an address is duplicated, an error
will occur.
Switch off the power before configuring the settings, or an
error will occur.
CAUTION
ENC1
1
0
2
3
4
6
5
7
2800 W
2200 W
Switch cord
Switch For setting the cooling output
Setting the cooling output
Note: Only
licensed
maintenance
personnel can
alter the cooling
output that is
set before
shipping.
Table: 8-1
8000 W
7100 W
5600 W
4500 W
3600 W
9000 W
9
14000 W
11200 W
10000 W8
B
A
12500 W
X1 X2)
E6
DC fan error
No address at the first
power on
Mode conflict
Comm. error with outdoor unit
Temp. sensor (T1)) error
Temp. sensor (T2) error
Temp. sensor(T2B) error
EEPROM error
Outdoor unit error
Ed
E4
E3
E2
E1
E0
FE
E7
Error Content
Error
Code
EEV coil error
Eb
Water level alarm
EE
8.3 Error Content
To wired controller