TOPVERT S1 Series
E-
9
FUNCTIONS and PARAMETER SUMMARY
★=This parameter cannot be set
during operation.
◎: Available in Firmware Version
2.xx and after only.
⊙: Available in Firmware Version
3.xx and after only.
{ }Parameter no. in
Firmware Version 1.xx
[ ] :optional
Group 0: System parameters
Parame
ters
Functions Settings
Factory
Setting
User
★ Pr0-00
Model display Display according to the model number Read Only
★ Pr0-01
Rated output current to
motor
Display according to the model number
Read Only
10: Parameter reset for 60Hz - 230/460V motor
application
9: Parameter reset for 50Hz - 220/380V motor
application
8: Parameter reset for 60Hz - 220/380V motor
application
7: Parameter reset for 50Hz - 230/460V motor
application
6: Parameter reset for 60Hz - 240/415V motor
application
◎
★ Pr0-02
Parameter Reset (Motor
V/F selecting)
5: Parameter reset for 50Hz - 240/415V motor
application
◎
8
Pr0-03
Password Input (The Key)
0〜9999
0
Pr0-04
Password set (The Lock)
0〜9999
0
0 All parameters are readable,
Bit0
1
Parameters after Pr0-05 cannot read
”Err” message will displayed when try
to read.
0
Enable Frequency Command.
Bit1
1 Disable frequency command
0 Enable run command from PU
Pr0-05 Parameter Locking Level
Bit2
1 Disable run command from PU
b00000
0: Frequency command value
1: Actual output frequency (Hz)
2: Output current
Pr0-06
Power on display
selection
3: User defined contents on Pr0-07
0
0: Motor speed (RPM)
1: DC-Bus Voltage (Vdc)
2: Actual output voltage (Vac)
3: Output voltage command value (Vac)
4: PID feedback frequency value (Hz)
5: Running step no. of MSS run
6: Sleep time (Pr8-07)
7: Auto-Restart after Fault (Pr6-10)
8: PID frequency command value (Hz)
9: (Factory Reserved)
10: Output power factor angle ( º )
11: Counter value
12: Over-Torque detection time 1 (Pr5-17)
13: (Factory Reserved)
14: Dwell Time at Accel. (Pr6-14)
15: Dwell Time at Decel. (Pr6-16)
16: DC Braking time in Start-up (Pr6-01)
Pr0-07 Versatile display
17: DC Braking Time during stop (Pr6-02)
0