TOPVERT S1 Series
E-
22
0: Cannot be switch during
operation.
Bit 0
1: Can be switch during operation.
0: No need to waiting for confirm
signal when swiching
◎ Pr5-49 Motor selection mode
Bit 1
1: Need to waiting for confirm
signal when swiching
b00000
Group 6: Special Parameters
Parame
ters
Functions Settings
Factory
Setting
User
Pr6-00 DC Braking Current Level Amp (0~125% of drive’s rated current) A(0%)
Pr6-01
DC Braking Time during
Start-up
0.00〜60.00 Sec 0.00
Pr6-02
DC Braking Time during
stopping
0.00〜60.00 Sec 0.00
Pr6-03
Start-point for DC Braking
during stopping
0.00〜600.00 Hz 0.00
Pr6-04
Increasing Rate of the DC
Braking Voltage
0.01~300.00% 50.00%
0:Operation stops after momentary power loss.
1:Operation continues after momentary power loss,
speed search Speed Search starts with Last
Output Frequency Downward
Pr6-05
Momentary Power Loss
Operation Selection
2:Operation continues after momentary power loss,
speed search starts with the Start-up frequency
Upward
0
Pr6-06
Maximum Allowable Power
Loss Time
0.1〜5.0 Sec 2.0
Pr6-07
Base-Block Time for Speed
Search (BB)
0.1〜5.0 Sec 0.5
Pr6-08
Maximum Current Level for
Speed Search
Amp (20〜200% of drive’s rated current) A(120%)
Pr6-09
Deceleration Time for Speed
Search
0.50〜120.00 Sec 3.00
Pr6-10 Auto Restart after Fault 0〜10 times 0
0:speed search disabled
1:speed search through the frequency command
2:FWD-speed search only
(motor only runs in FWD direction)
3:REV-speed search only
(motor only runs in REV direction)
4:FWD/REV speed search enabled in both
directions (FWD first)
Pr6-11 Speed Search during Start-up
5:REV/FWD speed search enabled in both
directions (REV first)
0
Pr6-12
Speed Search Frequency
(FWD direction)
0.00〜600.00 Hz
60.00/50.00
Pr6-13
Speed Search Frequency
(REV direction)
0.00〜600.00 Hz
60.00/50.00
Pr6-14 Dwell Time at Accel. 0.00~60.00 Sec 0.00
Pr6-15 Dwell Frequency at Accel. 0.00〜600.00 Hz 6.00
Pr6-16 Dwell Time at Decel. 0.00~60.00 Sec 0.00
Pr6-17 Dwell Frequency at Decel. 0.00〜600.00 Hz 6.00
Pr6-18 Dwell Frequency current Amp (0~150% of rated current) A(0%)
Pr6-19 Traverse Skip Frequency 0.00~100.00Hz 0.00
Pr6-20 The Amplitude of traverse 0.00~200.00Hz 0.00