8-10. Sensor Characteristics
Outdoor Unit
Temperature sensor characteristics
Temperature [°C]
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
Resistance [kΩ]
Temperature [°C] Resistance [kΩ]
101.7
76.3
57.7
44.0
33.8
26.1
20.4
16.0
13.0
10.0
8.0
6.4
5.2
4.2
3.5
2.8
2.3
1.9
1.6
1.4
1.1
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
162.2
125.8
98.3
77.5
61.5
49.1
39.5
32.0
26.1
21.4
17.6
14.6
12.1
10.2
8.5
7.2
6.1
5.2
4.5
3.8
3.3
2.9
2.5
2.2
1.9
Outdoor TD1, TD2, TK1 and TK2 sensors
Resistance
[kΩ]
(10 °C or below)
Resistance
[kΩ]
(10 °C or above)
Resistance
[kΩ]
(50 °C or below)
Resistance
[kΩ]
(50 °C or above)
10
15
25
5
20
0
10 20 30 40
50
60 70-10 0
Temperature [°C]
80 90 10003-02-
100
150
50
33.8kΩ
10.0kΩ
200
Temperature [°C]
200
0
10
20
5
15
0
01020304
70
80 90 100 110 120 130
50 60
100
150
50
0
Outdoor TS1, TS3, TE1, TE2, TE3, TL1, TL2, TL3 and TO sensors
Temperature [°C]
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
Resistance [kΩ]
98.9
74.1
56.1
42.8
33.0
25.6
20.0
15.8
12.5
10.0
8.0
6.5
5.3
4.4
3.6
3.0
2.5
2.1
1.7
1.5
1.3
Resistance
[kΩ]
(10 °C or below)
Resistance
[kΩ]
(10 °C or above)
10
15
25
5
20
0
-10 0
10 20 30 40
50
60 70
Temperature [°C]
80 90 100-30 -20
100
150
50
33.0kΩ
10.0kΩ
200
0
Outdoor TG1, TG2 and TG3 sensors
- 242 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba MMY-MUP1001HT8P and is the answer not in the manual?

Toshiba MMY-MUP1001HT8P Specifications

General IconGeneral
BrandToshiba
ModelMMY-MUP1001HT8P
CategoryAir Conditioner
LanguageEnglish

Related product manuals