EasyManuals Logo

Toshiba RAV-GP1601AT8-E User Manual

Toshiba RAV-GP1601AT8-E
109 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
– 22 –
3. OUTDOOR UNIT REFRIGERATING CYCLE DIAGRAM
In cooling operation
In heating operation
DIA 25 × L180
DIA 25 × L210
TS sensor
P
Pressure
switch
TO sensor
TE sensor
TD sensor
TL sensor
Cooling: High pressure
Heating: Low pressure
Cooling: Low pressure
Heating: High pressure
Check joint
Heat exchanger
DIA 8, 2 rows, 52 stages
FP1.45, flat fin
Accumulator
(2500cc)
Rotary compressor
(RX420A3F-27M)
PMV
Capillary
DIA 4 × DIA 3 (6 pcs.)
Strainer
Strainer
Refrigerant pipe
at liquid side DIA 9.5
Packed valve
Refrigerant pipe
at gas side DIA 15.9
Ball valve
Distributor
Muffler
Muffler
Muffler
This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
meter becomes 2 times of No. of compressor revolutions (rps).
RAV-GP1101 series
Pressure Pipe surface temperature
Compressor
drive revolution
frequency (rps)
Indoor fan
Indoor/outdoor
temp. condition
(Mpa) (kg/cm
2
G) Discharge Suction
Indoor heat
exchanger
Outdoor heat
exchanger
Pd Ps Pd Ps (TD) (TS) (TC) (TL) (TE) Indoor Outdoor
Heating
Cooling
Standard
Overload
Low load
Standard
Overload
Low load
2.3
3.1
2.2
2.5
3.4
2.0
1.1
1.5
0.7
0.8
1.4
0.2
23.5
32.0
22.6
25.9
35.1
20.0
11.7
14.8
7.4
8.2
13.8
1.7
80.2
67.0
70.0
87.2
77.0
78.0
12.9
17.0
2.0
3.2
20.0
-25.0
11.0
16.0
1.0
41.0
53.0
31.0
44.6
48.0
36.0
7.6
22.0
-10.0
36.9
47.0
16.0
3.0
19.0
-23.0
36.6
35.4
33.0
40.2
26.4
90.6
HIGH
HIGH
LOW
HIGH
LOW
HIGH
27/19
32/24
18/15.5
20/-
30/-
15/-
35/-
46/-
-15/-
7/6
24/18
-20/-
RAV-GP1401 series
Pressure Pipe surface temperature
Compressor
drive revolution
frequency (rps)
Indoor fan
Indoor/outdoor
temp. condition
(Mpa) (kg/cm
2
G) Discharge Suction
Indoor heat
exchanger
Outdoor heat
exchanger
Pd Ps Pd Ps (TD) (TS) (TC) (TL) (TE) Indoor Outdoor
Heating
Cooling
Standard
Overload
Low load
Standard
Overload
Low load
2.4
3.3
2.2
2.7
3.3
1.9
1.0
1.3
0.7
0.8
1.2
0.2
24.0
34.0
22.7
27.8
34.1
19.5
10.6
13.4
7.5
8.2
12.3
1.7
89.7
73.0
71.0
90.8
76.0
77.0
9.3
18.0
3.0
1.5
17.0
-25.0
8.0
17.0
2.0
44.0
52.0
30.0
46.8
51.0
37.0
7.6
20.0
-10.0
37.6
50.0
16.0
2.7
17.0
-23.0
50.4
42.0
33.0
51.6
26.4
90.6
HIGH
HIGH
LOW
HIGH
LOW
HIGH
27/19
32/24
18/15.5
20/-
30/-
15/-
35/-
46/-
-15/-
7/6
24/18
-20/-
RAV-GP1601 series
Pressure Pipe surface temperature
Compressor
drive revolution
frequency (rps)
Indoor fan
Indoor/outdoor
temp. condition
(Mpa) (kg/cm
2
G) Discharge Suction
Indoor heat
exchanger
Outdoor heat
exchanger
Pd Ps Pd Ps (TD) (TS) (TC) (TL) (TE) Indoor Outdoor
Heating
Cooling
Standard
Overload
Low load
Standard
Overload
Low load
2.4
3.4
2.2
3.0
3.2
1.9
1.0
1.2
0.8
0.8
1.2
0.2
24.1
35.0
22.7
30.5
33.0
19.5
10.3
12.2
7.6
8.2
12.3
1.7
98.6
77.0
72.0
100.9
75.0
77.0
8.7
19.0
4.0
0.7
17.0
-25.0
7.0
18.0
3.0
48.0
51.0
30.0
48.4
54.0
37.0
7.6
20.0
-10.0
38.3
53.0
17.0
2.4
17.0
-23.0
61.2
48.6
33.0
60.0
26.4
90.6
HIGH
HIGH
LOW
HIGH
LOW
HIGH
27/19
32/24
18/15.5
20/-
30/-
15/-
35/-
46/-
-15/-
7/6
24/18
-20/-

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba RAV-GP1601AT8-E and is the answer not in the manual?

Toshiba RAV-GP1601AT8-E Specifications

General IconGeneral
BrandToshiba
ModelRAV-GP1601AT8-E
CategoryAir Conditioner
LanguageEnglish

Related product manuals