■Specifications
3 SYSTEM CONFIGURATION
■System design pattern
The following table shows the connectivity of 3
rd
party Dx-Coil by capacity.
Available up to 8ton (096type)
•Diversity (Capacity ratio between indoor unit and outdoor unit) is 60% to 110% when Dx-Coil is connected.
•Two or more Dx-Coil up to 8ton combination is available.
•Two Dx-Coil over 8ton combination is available on 28 and 32ton.
•Combination of Dx-Coil up to 8ton with VRF indoor unit (up to 8ton) is available.
•Combination of Dx-Coil over 8ton with VRF indoor unit (up to 8ton) is prohibited
•Wired remote controller is necessary when capacity code setting.
Ambient operating temperature range (*1)
Ambient operating humidity range (*1)
10 to 90% (Non-condensing)
Storage temperature range
(*1) Install in the place avoiding direct sunlight and rain