13
E6582171
Set parameters of resolver
Table 3-2. Parameters of resolver
(1) <F397: Resolver carrier frequency> is the excitation carrier frequency of resolver signal.
(2) Set <F376: PG select> to “3” when polarity is positive, or “13” when polarity is negative.
(3) <F377: PG option disconnection detection>=“1” : in case resolver is not connected, or resolver at least one phase is
missed, “E-12” trip occurs. (<F376> should be set for Resolver)
It is necessary to reset the inverter power to enable the changes.
(4) Use resolver with transformation ratio = 0.5
(5) Use resolver with 2 poles
Title Function Name Parameter Setting Default Setting
F376 PG select
0: PTI (Command) – PTI (FB)
1: PTI (Command) – Digital option (FB)
2: -
3: PTI (Command) - Resolver option (FB)
4 - 5: -
6: Digital option (Command) - Non FB
7 - 9: -
10: PTI (Command) - PTI (FB inversion)
11: PTI (Command) - Digital option (FB inversion)
12: -
13: PTI (Command) - Resolver option (FB inversion)
14 - 15: -
16: Digital option (Command inversion) - Non FB
0
F377
PG option disconnection
detection
0: Disabled
1: Enabled
0
F397 Resolver carrier frequency 3 - 12 10

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS3
CategoryInverter
LanguageEnglish

Related product manuals