E6581386
F-36
6
Set  at *2
(After execution, the setting returns
to .)
 is displayed.
The base frequency or the rated
rotational speed of the motor is
not set correctly. Check their
settings.
Enter the correct value for 
or , and then set
 to again.
Set the following parameters, as specified on the motor nameplate.
Nameplate
information
Title Setting range
Base frequency


~

Hz
Base frequency
voltage


~

(200V )

~

(400V )
Rated capacity
of motor


~

kW
Motor rated
current

~A
Motor rated
speed

~
min-1
The following parameters have
been calculated and set.
 Motor constant 1
 Motor constant 2
 Motor constant 3
 Motor constant 4
End
NO
YE
S
NO
YES
 and  have been
tuned to the motor connected.
Parameters  and
 use the value
calculated automatically by the
End
 or
 is displayed.
End
YES
NO
Is the motor Toshiba standard
four-pole motor with the same
capacity rating as the inverter?
Is the motor cable 30m or less
in length? *1
Operation in automatic torque
boost mode or vector control
mode
(=, , , , )
Check the precautions to be taken
when setting the auto tuning
parameter to 1, and if no problem
is found, then set  to
and start operation.
Is the motor actually
connected and in a
standby state?
YES
NO
Make necessary settings, as
specified in (1) Setting auto-tuning.
End
*3
*2: No problem even if the motor is not connected.
*3: It does not matter whether the motor is under load or no-load
conditions.
*4: As for models 200V-55kW or more and 400V-90kW or more,
also "

" and "

"is set.
For details of each parameter, see
the next page.
*4
*1:
Motor used
Type No. of motor poles
Capacity
Tuning required or not
(Yes in flowchart: Tuning required, No: Tuning not required)
Same as the inverter capacity * Not required (tuned to factory defaults)
4P
Different from the inverter capacity
Same as the inverter capacity
Toshiba
standard
motor
Other than 4P
Different from the inverter capacity
Others
Required
* When using a long cable (guide: 30m or over), be sure to make auto-tuning 1 (=).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals