E6581386
F-64
6
6.30.2 Setting of optional meter outputs
 ~  ,  ~  : Meter output settings
For details, refer to Instruction Manual (E6581341) specified in Section 6.36.
6.30.3 Calibration of analog outputs
 : FM voltage/current output switching
 ,  : FM output gradient characteristic and bias adjustment
 ,  : AM output gradient characteristic and bias adjustment
Function
Output signals from FM/AM terminals are analog voltage signals. Their standard setting range is from 0 to
10Vdc.
The output current from terminal FM can be changed to 0 to 20mAdc (or 4 to 20mAdc) by changing the settings
of terminal SW2 and a parameter.
[Parameter setting]
Title Function Adjustment range Default setting

FM voltage/current output
switching
: Voltage 0~10V output
: Current 0~20mA output


FM output gradient
characteristic
: Negative gradient
(descending)
: Positive gradient
(ascending)

 FM bias adjustment -. % 

AM output gradient
characteristic
: Negative gradient
(descending)
: Positive gradient
(ascending)

 AM bias adjustment -. % 
Note: To switch to 0-20mAdc (4-20mAdc), set  to .
FM terminals setting example

,

=

=
(%)

,

=

=

(%)
20
0
0
Internal calculated value
100%
0
Internal calculated value
100%


4
Output current
(mA)
20
Output current
(mA)


=

=

=

(%)

=

=

=

(%)
20
0
0
Internal calculated value
100%
0 100%

: Large gain

:Small gain
4
Output current
(mA)
20
Output current
(mA
)


Internal calculated value
SW2: 0-10V/0-20mA side
SW2: 0-10V/0-20mA side
SW2: 0-10V/0-20mA side
SW2: 0-10V/0-20mA side
The analog output inclination can be adjusted using the parameter 
For code data 50 to 64, negative inclination is invalid.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals