E6581386
I-5
9
(Continued)
Requirements
Inverter type
PWM carrier
frequency

(kHz)
Length of motor
connecting cable
(m)
Conducted noise
IEC61800-3 category C2
(EN55011 classA Group1)
Applicable filters
Conducted noise
IEC61800-3 category C1
(EN55011 classB Group1)
Applicable filters
100 EMF3-4072E EMF3-4072E
2~4
300 EMF3-4072E -
100 EMF3-4072E EMF3-4072E
VFPS1-4150PL,
VFPS1-4185PL
4.1~12
200 EMF3-4072E -
100 EMF3-4090F EMF3-4090F
2~4
300 EMF3-4090F -
100 EMF3-4090F EMF3-4090F
VFPS1-4220PL
4.1~12
200 EMF3-4090F -
100 EMF3-4092G EMF3-4092G
2~2.5
300 EMF3-4092G -
100 EMF3-4092G EMF3-4092G
VFPS1-4300PL
VFPS1-4370PL
2.6~12
200 EMF3-4092G -
100 EMF3-4180H EMF3-4180H
2~2.5
300 EMF3-4180H -
100 EMF3-4180H EMF3-4180H
VFPS1-4450PL~
VFPS1-4750PL
2.6~12
200 EMF3-4180H -
VFPS1-4900PC~
VFPS1-4160KPC
2.5 100 EMF3-4300I -
VFPS1-4220KPC~
VFPS1-4315KPC
2.5 100 EMF3-4600J -
VFPS1-4400KPC 2.5 100 EMF3-4800K -
VFPS1-4500KPC,
VFPS1-4630KPC
2.5 100 EMF3-4600J × 2 -
(2) Use shielded cables for the power and control cables, including filter input cables and inverter output cables.
Route the cables and wires so as to minimize their lengths. Keep a distance between the power cable and the
control cable and between the input and output wires of the power cable. Do not route them in parallel or bind
them together, instead cross at right angle.
(3) Install the filter and the inverter in an enclosed steel cabinet, it is more effective in limiting the radiation. Earth the
cabinet body securely with the thickest and shortest possible electric wire installed away from the power cables.
(4) Route the EMC filter input and output wires apart from each other.
(5) To limit the radiation noise from cables, earth each shielded cable to the EMC plate. It is effective to earth
shielded cables in the vicinity of the inverter and filter (within a radius of 10cm from each of them). Inserting a
ferrite core in a shielded cable is even more effective in limiting the radiation noise.
(6) To further limit the radiation noise, insert a zero-phase reactor in the inverter output line and insert ferrite cores in
the earth cables of the EMC plate and cabinet.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals