K-3
E6581386
11
2. Basic parameter [3/4] Sensorless vector/PG feedback control (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
Setting Motor type
Overload
protection
OL stall
0 (protect) × (not stall)
1 (protect) (stall)
2 × (not protect) × (not stall)
3
Standard
Motor
× (not protect) (stall)
4 (protect) × (not stall)
5 (protect) (stall)
6 × (not protect) × (not stall)
 0017
Electronic thermal protection
characteristic selection
7
VF Motor
× (not protect) (stall)
1/1 0 Enabled / 5. 14
 0701 Current/voltage unit selection
0:%
1:A (ampere)/V (volt)
1/1 0 Enabled / 5. 15
 0005 FM terminal meter selection 0~76 *1 1/1 0 Enabled / 5. 16
 0006 FM terminal meter adjustment - 1/1 *4 Enabled / 5. 16
 0670 AM terminal meter selection 0~76 *1 1/1 2 Enabled / 5. 16
 0671 AM terminal meter adjustment - 1/1 *4 Enabled / 5. 16
 0300 PWM carrier frequency 1.0~16.0kHz (2.5~8.0kHz) *2 0.1/0.1 *3 Enabled / 5. 17
 0301 Auto-restart control selection
0:Disabled
1:At auto-restart after momentary stop
2:When turning ST on or off
3:1+2
4:At start-up
1/1 0 Disabled / 5. 18.1
 0302
Regenerative power ride-through
control
0:Disabled
1:Power ride-through
2:Deceleration stop during power failure
1/1 0 Disabled / 5. 18. 2
Setting
Braking function ST-off
overload
detect
0 Disabled
1 protect
2
Enabled
not protect
3 protect
4
Enabled
(It is effective
in trip
condition.)
*5)
Disabled
not protect
5 protect
6
Enabled
not protect
7 protect
 0304 Dynamic braking selection
8
Enabled
(It isn't
effective in
trip.condition )
Disabled
not protect
1/1 0 Disabled / 5. 19
*1: For the adjustment range, see the table on page K-35.
*2: For 200V-55kW to 200V-90kW models and 400V-90kW to 400V-630kW models, the carrier frequency is between 2.5 and 8.0kHz inclusive.
*3: Default values vary depending on the capacity. See the table of K-42.
*4: Default setting value is adjusted for connection of frequency meters "QS60T". (Between FM and CCA: Approx. 3.6V) (Between AM and CCA: Approx. 3.6V)
*5: The state of olr trip is excluded.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals