E6581386
L-2
12
2) Standard specifications (large capacity types) [Note 1]
Item
Specification
Voltage class
200V class
Applicable motor (kW)
55 75 90
Applicable motor (HP)
75 100 125
Type VFPS1-
Form 2550P 2750P 2900P
Output capacity
(kVA) [Note 2]
84 109 137
Output current
(A)
221 285 359
Output voltage Three-phase 200V~240V (The maximum output voltage is equal to the input supply voltage.)
Rating
Overload
current rating
120%-1 minute, 135%-2 sec.
Dynamic braking
circuit
Built-in dynamic braking drive circuit
Electrical
brakin
Dynamic braking
resistor
An external braking resistor (optional)
Rating: Refer to 5.19.
Voltage-frequency
[Note 3]
Three-phase 200~240V-50/60Hz
Power
su
l
Allowable
fluctuation
Voltage + 10% - 15% [Note 4] Frequency ±5%
Protective method IP00 (IEC60529) [Note 5]
Cooling method Forced air-cooled
Cooling fan noise (dBA)
61 61 70
Color RAL7016
EMC filter
External filter (optional)
DC reactor
Attached DC reactor
Item
Specification
Voltage class
400V class
Applicable motor (kW)
90 110 132 160 220 250 280 315 400 500 630
Applicable motor (HP)
125 150 200 250 350 400 450 500 600 700 1000
Type VFPS1-
Form 4900PC 4110KPC 4132KPC 4160KPC 4220KPC 4250KPC 4280KPC 4315KPC 4400KPC 4500KPC 4630KPC
Output capacity
(kVA) [Note 2]
136 164 197 239 325 367 419 469 578 717 905
Output current
(A)
179 215 259 314 427 481 550 616 759 941 1188
Output voltage Three-phase 380V~480V (The maximum output voltage is equal to the input supply voltage.)
Rating
Overload
current rating
120%-1 minute, 135%-2 sec.
Dynamic
braking circuit
Built-in dynamic braking drive circuit External dynamic braking circuit (optional)
Electrical
brakin
Dynamic braking
resistor
An external braking resistor (optional)
Rating: Refer to 5.19.
Voltage-frequency
[Note 3]
Three-phase
380~480V-50/60Hz
Three-phase 380~440V-50Hz
Three-phase 380~480V-60Hz
Power
su
l
Allowable
fluctuation
Voltage + 10% - 15% [Note 4] Frequency ±5%
Protective method IP00 (IEC60529) [Note 5]
Cooling method Forced air-cooled
Cooling fan noise (dBA)
61 61 72 73 73 76 76 76 76 76 78
Color RAL7016
EMC filter
Built-in
DC reactor
Attached DC reactor
Note 1: For 200V-55kW, 400V-90kW or larger model, be sure to install DC reactor.
However, this is unnecessary for DC input specifications.
Note 2: Capacity is calculated at 220V for the 200V models and at 440V for the 400V models.
Note 3: An external power supply backup available (optional) (Type: CSP002Z)
Note 4: ±10% when the inverter is used continuously (load of 100%).
Note 5: Models, 200V-18.5kW and above, and 400V-22kW and above, do not have wiring port covers. They have
large openings, but there is no space to bend the external cables inside the unit.