EasyManuals Logo
Home>Toshiba>Power Supply>TOSVERT VF-PS1

Toshiba TOSVERT VF-PS1 User Manual

Toshiba TOSVERT VF-PS1
317 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
E6581386
A-18
1
Method of lubricating load mechanisms
Operating an oil-lubricated reduction gear and gear motor in the low-speed areas will worsen the lubricating effect.
Check with the manufacturer to find out about operable speed range.
Low loads and low inertia loads
The motor may demonstrate instability such as abnormal vibrations or overcurrent trips at light loads of 5% or
under of the rated load, or when the load's moment of inertia is extremely small. If that happens reduce the carrier
frequency.
Occurrence of instability
Unstable phenomena may occur under the load and motor combinations shown below.
• Combined with a motor that exceeds applicable motor ratings recommended for the inverter
• Combined with special motors
To deal with the above lower the settings of inverter carrier frequency. (When performing vector control, set the
carrier frequency at 2kHz or more. If the carrier frequency is set below 2kHz, it will be automatically corrected to
2kHz by the inverter.)
Minimum carrier frequency for 200V-55kW and above, 400V-90kW and above models is 2.5kHz.
• Combined with couplings between load devices and motors with high backlash
In this case, set the S-pattern acceleration/deceleration function and adjust the response time inertial moment
setting during vector control or switch to V/f control (
=).
• Combined with loads that have sharp fluctuations in rotation such as piston movements
In this case, adjust the response time inertial moment setting during vector control or switch to V/f control (
=).
Braking a motor when power supply is lost
A motor with its power cut off goes into freewheel, and does not stop immediately. To stop the motor quickly as
soon as the power is cut off install an auxiliary brake. There are different kinds of brake devices, both electrical and
mechanical. Select the brake that is best for the system.
Loads that generate negative torque
When combined with loads that generate negative torque the protection for overvoltage and overcurrent on the
inverter will go into operation and may cause a trip. For this kind of situation, you must install a dynamic braking
resistor, etc. that complies with the load conditions.
Motor with brake
If a brake motor is used with the braking circuit connected to the output terminals of the inverter, the brake cannot
be released because of a voltage drop at startup. Therefore, when using the inverter along with a brake motor,
connect the braking circuit to the power supply side of the inverter, as shown in the figure below. In most cases, the
use of a brake motor causes an increase in noise at low-speed.
B
IM
LOW
OUT1
     
P24
Three-
phase
power
supply
MC2
MC3
MC2
MC1
MC2
B
IM
MC3
MC1
MC3
FLB
FLC
PWR
P24
Three-
phase
power
supply
LOW
(Non-exciting brake)
(Non-exciting brake)
MC1
MC2
Circuit configuration 1 Circuit configuration 2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals