E6581611
F-45
6
6.11.2 Run/stop control with frequency command
f241 : Operation starting frequency
f242 : Operation starting frequency hysteresis
Function
The Run/stop of operation can be controlled simply with frequency command.
[Parameter setting]
Title Function Adjustment range Default setting
f241
Operation starting frequency 0.0-fh (Hz) 0.0
f242
Operation starting frequency hysteresis 0.0-fh (Hz) 0.0
0 A B 100% Frequency command value
+
-
When the frequency command signal
reaches the B point, the inverter
operates.
When decelerating, operation stops
when the frequency setting signal is less
than point A.
Output frequency [Hz]