E6581611
F-120
6
6.33 Adjustment parameters
6.33.1 Inputting integral input power pulse
 : Integral input power pulse output unit
 : Integral input power pulse output width
Function
Pulse signal can be output each time integral input power reaches integral power unit that is set by
f667.
Pulse output width is set by
f668.
[Parameter setting]
Title Function Adjustment range Default setting

Integral input power pulse output unit
0: 0.1kWh
1: 1kWh
2: 10kWh
3: 100kWh
1

Integral input power pulse output width
0.1-1.0 (s)
0.1
Setting example) When integral input power pulse is output from output terminal
Title Function Adjustment range Setting

Output terminal selection 2A 0 - 255
180:
IPU (Integral input
power pulse output signal)
There is no reverse signal.
6.33.2 Pulse train output for meters
f669 : Logic output/pulse train output selection (OUT)
f676 : Pulse train output function selection (OUT)
f677 : Maximum numbers of pulse train output
f678 : Pulse train output filter
Function
Pulse trains can be sent out through the OUT output terminals.
Set a pulse output mode and the number of pulses.
Ex.: When operations frequencies (0 to 60Hz) are put out by means of 0 to 600 pulses
fh=60.0, f669=1, f676=0, f677=0.60
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VFS15-4037PL-W and is the answer not in the manual?

Toshiba TOSVERT VFS15-4037PL-W Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VFS15-4037PL-W
CategoryInverter
LanguageEnglish

Related product manuals