<Example of operation>
1) Output terminal function: 28 (OT) Over-torque detection
f615=0 (Alarm only)
Time [sec]


Torque (%)
Over-torque
signal output
less than


ON
OFF
OFF
When
f615 = 1 (tripping), the inverter will trip if over-torque lasts for the period of time set with
f618. The over-torque signal remains ON.
6.29.11 Cooling fan control selection
f620 : Cooling fan ON/OFF control
Function
Operate the cooling fan only when the ambient temperature is high or during operation. This function
will extend the service life of the cooling fan than when it is always running while the power is ON.
f620=0: Cooling fan automatically controlled. Cooling fan operates only when the ambient temperature is
high during operation.
f620=1: Cooling fan not automatically controlled. The fan is always running when the inverter is on.
If the ambient temperature is high, even when the inverter is stopped, the cooling fan automatically
operates.
[Parameter setting]
Title Function Adjustment range Default setting
f620
Cooling fan ON/OFF control
0: ON/OFF control
1: Always ON
2-7: -
0
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VFS15-4037PL-W and is the answer not in the manual?

Toshiba TOSVERT VFS15-4037PL-W Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VFS15-4037PL-W
CategoryInverter
LanguageEnglish

Related product manuals