E6581611
F-108
6
6.29.10 Over-torque trip
f615 : Over-torque trip/alarm selection
f616 : Over-torque detection level
f618 : Over-torque detection time
f619 : Over-torque detection hysteresis
ï‚· Function
If the torque value exceeds the value set at f616 and doesn’t return below f616-f619
for a time that exceeds the value set at f618, tripping or output alarm will be activated.
ot is displayed in the event of a trip.
f615=0: No tripping. (Failure signal FL not activated)
An over-torque alarm can be put out by setting the output terminal function selection parameter.
f615=1: The inverter trips when a torque exceeding the f616-specified level has been detected for
longer than the f618-specified time. (Failure signal FL activated)
[Parameter setting]
Title Function Adjustment range Default setting
f615
Over-torque trip/alarm selection
0: Alarm only
1: Tripping
0
f616
Over-torque detection level
0 (disabled),
1-250 (%)
150
f618
Over-torque detection time 0.0-10.0 (s) Note 0.5
f619
Over-torque detection hysteresis 0-100 (%) 10
Note 1) If f616 is set to 0(disabled), the alarm is not activated regardless of the f615 setting.
Note 2) f618= 0.0 seconds is the shortest time detected on control.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VFS15-4037PL-W and is the answer not in the manual?

Toshiba TOSVERT VFS15-4037PL-W Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VFS15-4037PL-W
CategoryInverter
LanguageEnglish

Related product manuals