E6581611
C-5
3
3.2.1 How to run and stop
[Example of setting procedure]
Panel operation LED display Operation
Displays the output frequency (operation stopped).
(When standard monitor display selection f710=0 [output frequency])
auh
Displays the first basic parameter [History (auh)].
cmod
Turn the setting dial, and select "cmod".
1
Press the center of the setting dial to read the parameter value.
(Standard default: 1).
0
Turn the setting dial to change the parameter value to 0 (terminal block).
0cmod
Press the center of the setting dial to save the changed parameter.
cmod and the parameter set value are displayed alternately.
(1) Run and stop using the panel keypad (cmod=1)
Use the
and keys on the panel keypad to start and stop the motor.
: Motor runs. : Motor stops.
●The direction of rotation is determined by the setting of parameter (forward run, reverse run selection).
(: forward run, : reverse run)
●Forward run and reverse run are switchable with the extension panel (option). Set the parameter fr
(forward run, reverse run selection) to 2 or 3. (Refer to section 5.8)
(2) RUN and STOP using external signals (cmod=0): Sink (Negative) logic
Use external signals to the inverter terminal block to start and stop the motor.
Frequency
ON
OFF
F-CC
Slow down
and stop
F
Short
and terminals: run forward
Open and terminals: slow down and stop
CC
F CC
MODE
RUN
RUN
STOP
STOP