21
Installation (Continued)
Table 3-3
Customer Connection Wire Range
Table 3-4
Unit Electrical Data
Allowable Minimum Maximum Dual Condenser Fan Motors
Unit Rated Voltage Circuit Fuse Element HP FLA LRA KW
Size Voltage Range Ampacity Size Fuse Qty. (Each) (Each) (Each) (Each)
200/230/60/3 180-220/208-254 9.2 15 15 2 1.0 4.1 20.7 0.9
C20 460/60/3 416-508 4.1 15 15 2 1.0 1.8 9.0 0.9
575/60/3 520-635 3.2 15 15 2 1.0 1.4 7.2 0.9
200/230/60/3 180-220/208-254 13.3 20 15 3 1.0 4.1 20.7 0.9
C25 460/60/3 416-508 5.9 15 15 3 1.0 1.8 9.0 0.9
575/60/3 520-635 4.6 15 15 3 1.0 1.4 7.2 0.9
200/230/60/3 180-220/208-254 13.3 20 15 3 1.0 4.1 20.7 0.9
C30 460/60/3 416-508 5.9 15 15 3 1.0 1.8 9.0 0.9
575/60/3 520-635 4.6 15 15 3 1.0 1.4 7.2 0.9
200/230/60/3 180-220/208-254 17.4 20 20 4 1.0 4.1 20.7 0.9
C40 460/60/3 416-508 7.7 15 15 4 1.0 1.8 9.0 0.9
575/60/3 520-635 6 15 15 4 1.0 1.4 7.2 0.9
200/230/60/3 180-220/208-254 25.6 30 30 6 1.0 4.1 20.7 0.9
C50 460/60/3 416-508 11.3 15 15 6 1.0 1.8 9.0 0.9
575/60/3 520-635 8.8 15 15 6 1.0 1.4 7.2 0.9
200/230/60/3 180-220/208-254 25.6 30 30 6 1.0 4.1 20.7 0.9
C60 460/60/3 416-508 11.3 15 15 6 1.0 1.8 9.0 0.9
575/60/3 520-635 8.8 15 15 6 1.0 1.4 7.2 0.9
Notes:
1. Electric information is for each individual motor.
2. Minimum Circuit Ampacit
is 125% of the RLA of one motor plus the RLA of the remainin
motors.
3. Maximum Fuse Size is 300% of the RLA of one motor plus the RLA of the remaining motors.
4. Recommended Dual Element Fuse Size is 225% of the RLA of one motor plus the RLA of the remaining motors.
5. RLA is rated in accordance with UL Standard 465.
6. Local codes may take precedence.