General Information
CLCH-SVX014B-EN 7
Description
The gas heat section consists of an inshot tubular heat
exchanger gas train components, and a control panel for
electrical connections. It is an integral part of the entire air-
handling system.
An access door is provided for service and maintenance of
the burner and gas train components.
The gas heat section must be in a blow-thru position
downstream from the supply fan. Downstream sections
must be separated by a blank access section and discharge
temperatures must be controlled so as not to exceed the
temperature limits of components in the downstream
sections.
Table 1. Motor and electrical specifications
Specifications Gas Heater Input Power Inducer Motor
(a)
Control Power(a)
Volts 115 115
Hertz 60 60 60
Phase 11
HP n/a n/a
FLA/Amps n/a 6
(a) Powered by a “line to 115 volt” transformer for all gas heaters except 115/60/1 rated units.