EasyManuals Logo
Home>Trane>Chiller>CVHG

Trane CVHG Troubleshooting

Trane CVHG
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
CVHE-SB-32A 21
~ Stepper module must be X-13650455-04 or newer.
14 Starter module X-13650453-13 and greater have a less sensitive MPL diagnostic trip point.
Problem 49: Motor winding temperatures changing rapidly and randomly.
Corrective Action:
1 Electrical noise problem in the Circuit module. X-13650451-04 Rev. D or later corrects the
problem by adding a filtering circuit.
Problem 50: Differential Oil Pressure Calibration Diagnostic following post lube. Second-
ary problem may be the oil pump will not shut off after post lube.
Corrective Action:
1 Diagnostics are active in all non-running modes and the unit has been off for 5 minutes. The
UCP2 calibrates the oil pressure sensors and if an error is found greater than 3 PSID a
diagnostic is called out.
~ Sensors
~ Changing system pressures caused by such things as a pressure or changing water temper-
atures.
2 If the oil pump is running and will not shut off in post lube, the problem is a wiring error on the
Starter module. One or both of the following apply.
~ 115 VAC is connected to terminal J6-3 of the Starter module. Check to see if it was con-
nected incorrectly to Terminal J3-1.
~ Terminal J8 on the Starter module. J8-1 (Wire #13) goes to the 2K1 Contactor. J8-2 (Wire
#15) goes to 2K1 Auxiliary. Check to see if Wire #13 and Wire #15 are reversed.
Problem 51: Differential Oil Pressure
On Circuit module revision X-13650451-13 and newer, has a positive oil pressure
trip at 2/3 the setpoint with a default setpoint 12 psig and a minimum of 9 psig
setpoint.
Corrective Action:
1 The Circuit module was clearing the 3 minute oil pressure establish timer during a remote
RESET. This would result in an Oil Pressure Overdue diagnostic. (Exists for Circuit modules
X-13650451-06 and earlier).
2 Faulty oil pump motor.
3 Faulty 1F2 fuse.
4 Faulty Circuit module relay output.
5 Faulty oil pump capacitor.
6 Faulty oil pump sensor and/or wiring.
7 Clogged oil filter.
8 Faulty oil pressure regulator.
9 Differential oil pressure when the unit is off. The unit sees current due to Feedback via the
PFCCs or CTs. We get a starter interrupt failure. The UCP2 thinks the motor is running and
brings on the oil pump and logs differential oil pressure diagnostics.

Table of Contents

Other manuals for Trane CVHG

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane CVHG and is the answer not in the manual?

Trane CVHG Specifications

General IconGeneral
BrandTrane
ModelCVHG
CategoryChiller
LanguageEnglish

Related product manuals