RT-SVX36G-EN 53
Installation
O/A Sensor & Tubing Installation
An Outside Air Pressure Sensor is shipped with all units designed to operate on variable air volume
applications, units equipped with a return fan, or constant volume units with 100% modulating
exhaust w/Statitrac.
On VAV systems, a duct pressure transducer (3U60) and the outside air sensor is used to control
the discharge duct static pressure to within a customer-specified parameter.
On CV & VAV units equipped with 100% modulating exhaust w/Statitrac, a space pressure
transducer (3U62) and the outside air sensor is used to control the exhaust fan and dampers to
relieve static pressure to within a customer-specified parameter within the controlled space.
On units equipped with a return fan, a return pressure transducer (3U106) is connected to the
O/A sensor for comparison with return plenum pressure.
Refer to Figure 23, p. 56 and the following steps to install the sensor and the pneumatic tubing.
1. Remove the O/A pressure sensor kit located inside the filter section. The kit contains the
following items;
O/A static pressure sensor with sensor mounting
Bracket
50' of 3/16” O.D. pneumatic tubing
Mounting hardware
Figure 22. Removing supply and exhaust fan assembly shipping hardware (90-130 Ton)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak SAHL Series and is the answer not in the manual?

Trane IntelliPak SAHL Series Specifications

General IconGeneral
BrandTrane
ModelIntelliPak SAHL Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals